IGF::OT::IGF FOR OTHER FUNCTIONS THE CONTRACTOR SHALL PROVIDE THE NECESSARY SUPERVISION, LABOR AND MATERIAL TO REPAIR THE AC UNIT IN PHONE ROOM 3181. REPLACE 120V CONDENSER PUMP, 3/8 LIQUID LINE DRAIN, 3/8 SOLENOID VALVE, 24V SOLENOID VALUE AND LIQUID LINE DRYER. REMOVE REFRIGERANT CHARGE, WELD IN NEW LIQUID LINE DRYER AND SOLENOID VALUE. LEAK CHECK UNIT, PLACE SYSTEM IN DEEP VACUUM, RESTORE CHARGE BACK INTO SYSTEM. VERIFY THAT THE CONDENSER PUMP CAUSED FAILURE OF THE VALVE BY ONLY ALLOWING 7 VOLTS CONSTANTLY TO THE COIL CAUSING OVERHEATING. WORK TO BE PERFORMED AT CHET HOLIFIELD FEDERAL BUILDING, 24000 AVILA ROAD, LAGUNA NIGUEL, CA 92677.